One Relay /One Input
The PAD100-OROI uses one (1) SLC loop address when monitoring
one (1) Class B circuit and providing one (1) Form C relay contact.
The module mounts on either a 4” square or double gang box. The
module is capable of monitoring one (1) Class B circuit. The PAD100-
OROI includes one red LED to indicate the module’s status. In normal
condition, the LED flashes when the device is being polled by the
control panel. When a the input is activated, the LED will flash at a
fast rate.
Application
ThePAD100-OROI is compatible with Potter’s IPA and AFC/ARC
series addressable fire alarm control panels. The PAD100-OROI is an
interface module used to monitor dry contact devices such as sprinkler
waterflow, valve tamper switches, or conventional pull stations. The
module is capable of monitoring one Class B circuit. The PAD100-
OROI also provides one (1) form C relay contact.
Setting the Address
Each addressable SLC device must be assigned an address. The
address is set using the DIP switch located on the PAD100-OROI.
When the PAD100- OROI is used to monitor one Class B circuit
a single device address is assigned, the input and relay are then
identified as a sub-point of the module address. For example, if the
address number is assigned as “8”, the RLY1 relay will be “8.1” and
the IN1 input will be “8.2”.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Item#:
PAD100OROI
Manufacturer Item:
PAD100-OROI
Manufacturer:
Potter
You must be logged in to order this item. Log in here
The PAD100-RM uses one (1) SLC loop address to provide one (1)
Form C relay contact. The module mounts on either a 4” square or
double gang box. The PAD100-RM includes one red LED to indicate
the module’s status. In normal condition, the LED flashes when the
device is being polled by the control panel.
Application
The PAD100-RM is compatible with Potter’s IPA and AFC/ARC
series addressable fire alarm control panels. The PAD100-RM is an
interface module providing one (1) Form C relay contact.
Setting the Address
Each addressable SLC device must be assigned an address. The
address is set using the DIP switch located on the PAD100-RM. The
PAD100-RM uses a single device address to identify relay contacts.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Item#:
PAD100RM
Manufacturer Item:
PAD100-RM
Manufacturer:
Potter
You must be logged in to order this item. Log in here

3992707

Notification Appliance Circuit
The PAD100-NAC module uses one (1) address on an SLC Loop. The
module provides a programmable source of power to supervise and
control one (1) Class B or Class A Notification Appliance or one (1)
Class B Releasing Circuit. The module requires and supervises a 24
VDC auxiliary power connection. The PAD100-NAC includes one red
LED to indicate the module’s status. In normal condition, the LED
flashes when the device is being polled by the control panel.
Application
The PAD100-NAC is compatible with Potter’s IPA and AFC/ARC
series addressable fire alarm control panels. The PAD100-NAC is
a monitored Notification Appliance Circuit that wires to the SLC
loop to provide an additional notification circuit. When used with a
Potter addressable releasing panel, the PAD100-NAC can provide an
additional releasing circuit.
Setting the Address
Each addressable SLC device must be assigned an address. The
address is set using the DIP switches on the PAD100-NAC module.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits
Item#:
PAD100NAC
Manufacturer Item:
PAD100-NAC
Manufacturer:
Potter
You must be logged in to order this item. Log in here

3992709

LED With Keyswitch
The PAD100-LEDK provides a mappable key-switch input making it
ideal for key control of a variety of system functions. The PAD100-
LEDK provides mappable red LED which can be used to indicate a
variety of status conditions.
Application
The PAD100-LEDK is compatible with Potter’s IPA and AFC/ARC
series addressable fire alarm control panels. It installs on a single gang
box.
Setting the Address
The PAD100-LEDK uses one SLC address assigned to the device. The
address is set using the DIP switch located on the back of the PAD100-
LEDK device.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Item#:
PAD100LEDK
Manufacturer Item:
PAD100-LEDK
Manufacturer:
Potter
You must be logged in to order this item. Log in here

3992710

Addressable LED Module
The PAD100-LED uses one (1) SLC loop address when used as an
addressable indicator. The module mounts on either a 4” square or
double gang box. The PAD100-LED includes one red LED to indicate
the modules status. In normal condition, the LED flashes when the
device is being polled by the control panel. When activated, the LED
will flash at a fast rate.
Application
The PAD100-LED is compatible with Potter’s IPA and AFC/ARC
series addressable fire alarm control panels. The PAD100-LED is an
addressable LED module used to provide indication of a variety of
system conditions.
Setting the Address
Each addressable SLC device must be assigned an address. The address
is set using the DIP switch located on the PAD100-LED.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.

Item#:
PAD100LED
Manufacturer Item:
PAD100-LED
Manufacturer:
Potter
You must be logged in to order this item. Log in here
Item#:
PAD100DIM
Manufacturer Item:
PAD100-DIM
Manufacturer:
Potter
You must be logged in to order this item. Log in here
The PAD100-MIM is used to monitor the status of an initiating
device(s) that contain a normally open set of dry contacts. The module
is enclosed in a plastic case to protect against inadvertent shorts and
ground faults. The case can be mounted using a single screw. The
PAD100-MIM has a status indicator LED to indicate communication
and alarm condition. In normal condition, the LED flashes when the
device is being polled by the control panel. When the input is activated,
the LED will flash at a fast rate.
Application
The micro input module (PAD100-MIM) is compatible with Potter’s
IPA and AFC/ARC series addressable fire alarm control panels.
Generally the PAD100-MIM is used to monitor pull stations and
other devices where the module is installed in an electrical box or
enclosure behind the device being monitored.
Item#:
PAD100MIM
Manufacturer Item:
PAD100-MIM
Manufacturer:
Potter
You must be logged in to order this item. Log in here
The PAD100-IM module does not require an SLC loop address but does
consume power from the SLC loop. The module provides protection
against short circuits by limiting the number of affected devices. When
the PAD100-IM detects a short circuit on the SLC loop, it disconnects
the outgoing side of the module to prevent the short from affecting
the rest of the SLC loop. The PAD100-IM includes one red LED to
indicate the modules status. When the module is shorted, the LED will
light continuously. Once the short is removed, the PAD100-IM will
automatically restore to a cleared condition.
Application:
The PAD100-IM is compatible with Potter’s IPA series addressable fire
alarm control panels. The PAD100-IM is used to provide additional
reliability by isolating a segment of the SLC loop where a short circuit
has occurred.
Item#:
PAD100IM
Manufacturer Item:
PAD100-IM
Manufacturer:
Potter
You must be logged in to order this item. Log in here
The PAD100-SIM uses one (1) SLC loop addresses when monitoring
one (1) Class B circuit. The module mounts on either a 4” square or
double gang box. The module is capable of monitoring one (1) Class
B circuit. The PAD100-SIM includes one red LED to indicate the
module’s status. In normal condition, the LED flashes when the device
is being polled by the control panel. When the input is activated, the
LED will flash at a fast rate.
Application
The PAD100-SIM is compatible with Potter’s IPA and AFC/ARC
series addressable fire alarm control panels. The PAD100-SIM is an
interface module used to monitor dry contact devices such as sprinkler
waterflow, valve tamper switches, or conventional pull stations. The
module is capable of monitoring one Class B circuit.
Setting the Address
Each addressable SLC device must be assigned an address. The address
is set using the DIP switch located on the PAD100-SIM.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Item#:
PAD100SIM
Manufacturer Item:
PAD100-SIM
Manufacturer:
Potter
You must be logged in to order this item. Log in here
The PAD100-ZM module uses one (1) address on an SLC Loop when
monitoring two (2) Class B or one (1) Class A circuit. The module
requires and supervises a 24VDC auxiliary power connection. The
24VDC power source must be either a Potter IPA series addressable
panel, or a Potter PSN series power supply. The IDC may be wired
Class B or Class A which is selectable by an on board DIP switch. The
PAD100-ZM employs one red LED to indicate the module’s status. In
normal condition, the LED flashes when the device is being polled by
the control panel. When a device is activated, the LED will flash at a
fast rate.
Application
The PAD100-ZM is compatible with Potter’s IPA and AFC/ARC
series addressable fire alarm control panels. The PAD100-ZM is
used to supervise a zone of conventional 2-wire smoke detectors on
an Initiating Device Circuit (IDC). The PAD100-ZM is capable of
monitoring two (2) separate Class B or one (1) Class A circuits.
Setting the Address
Each addressable SLC device must be assigned an address. The
address is set using the DIP switch located on the PAD100-ZM. When
the PAD100-ZM is used to monitor two individual Class B circuits
a single device address is assigned, each input is then identified as a
sub-point of the module address. For example, if the address number
is assigned as “8”, the B1 input will be “8.1” and the B2 input will be
“8.2”.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Item#:
PAD100ZM
Manufacturer Item:
PAD100-ZM
Manufacturer:
Potter
You must be logged in to order this item. Log in here
The PAD100-TRTI uses one (1) SLC loop address when monitoring
two (2) Class B circuits or one (1) Class A circuit. The PAD100-TRTI
also provides two (2) Form C relay contacts. The module mounts
on either a 4” square or double gang box. The module is capable
of monitoring two (2) separate Class B circuits making it ideal for
monitoring sprinkler waterflow and valve tamper switches when they
are located in the same proximity. The PAD100-TRTI includes one
red LED to indicate the module’s status. In normal condition, the LED
flashes when the device is being polled by the control panel. When an
input is activated, the LED will flash at a fast rate.
Application
The PAD100-TRTI is compatible with Potter’s IPA and AFC/ARC
series addressable fire alarm control panels. The PAD100-TRTI is
an interface module used to monitor dry contact devices such as
sprinkler waterflow, valve tamper switches, or conventional pull
stations. The module is capable of monitoring two separate Class
B or one Class A circuits. The PAD100-TRTI also provides two (2)
form C relay contacts.
Setting the Address
Each addressable SLC device must be assigned an address. The
address is set using the DIP switch located on the PAD100-TRTI. The
he PAD100- TRTI is assigned a single device address, each input and
relay is identified as a sub-point of that single module address. For
example, if the address number is assigned as “8”, the RLY1 relay
will be “8.1”, the RLY2 relay will be “8.2, the B1 input will be “8.3”
and the B2 input will be “8.4”.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits